Reverse Osmosis System
Video
Product Images
Benefits
- Fully Equipped and Customizable
- Skid Mounted
- Components Easily Accessible
- Pre-Plumbed, Wired and Assembled
- Individually Tested and Preserved
- Low Operation and Maintenance Costs
- Easy Maintenance and Servicing
- 20% Less Energy than Standard Membranes
- 1-Year Limited Warranty
FEATURES
Models: M1– 4240, M1– 6240, M1–8240
-
S –150 Computer Controller
- LCD Backlit Display
- Pre-Treatment Lockout
- Tank Level Input
- Low and High Pressure Monitoring and Alarm
- Hour Meter
- Feed Flush
Models: M1–10240, M1–12240
-
S – 200 Computer Controller
- LCD Backlit Display
- Pre-Treatment Lockout
- Tank Level Input
- Low Pressure Monitoring and Alarm
- Hour Meter
- Dual TDS Monitoring
- Feed Flush
- Digital Flow Meters (3)
- Rejection Percentage
- Recovery Percentage
- AXEON Permeate and Concentrate Flow MetersA
- AXEON Concentrate Recycle Flow MeterA
- Stainless Steel Concentrate Globe Valve
- AXEON Pre-Filter 0-100 psi Panel Mounted Glycerin Filled Gauges
- AXEON Pump Discharge and Concentrate 0-300 psi Panel Mounted Glycerin Filled Gauges
- Pentair® Bag Filter Housing
- AXEON 5-Micron Filter Bag
- AXEON HF5–Series Ultra Low Energy Membrane Elements
- AXEON Bag Filter Housing with Stainless Steel Stand
- AXEON FRP– Series Membrane Housings (300 psi)
- Vertical Multi-Stage Stainless Steel Booster Pump
- Feed Solenoid Valve
- Feed Low Pressure Switch
- Clean-In-Place (CIP) Ports
- Permeate Sample Ports
- White Powder Coated Aluminum Frame
- Wooden Shipping Crate
OPTIONS AND UPGRADES
- S –150 Expander Board A
- S –150 Dual TDS Board A
- S – 200 Computer Controller A
- AXEON NF3 – Series Nanofiltration Membrane Elements
- AXEON NF4 – Series Nanofiltration Membrane Elements
- Hanna® BL 982411 ORP Meter A
- Hanna® BL 981411 pH Meter A
- S – 200 ORP Monitoring A
- S – 200 pH Monitoring A
- Chemical Pump Outlet
- Blending Valve
- High Pressure Tank Switch
- Pump Pressure Relief Valve B
- Caster Wheels
- Permeate Divert Valve
- Variable Frequency Drive
A. Only available on the following models: M1–4240, M1–6240, M1–8240
B. Standard for all 50Hz Systems
ARRAY SPECIFICATIONS
MODELS | Vessel Array | Vessel Size | Vessel Quantity | Membrane Size | Membrane Quantity |
---|---|---|---|---|---|
M2– 4240 | 2:2 | 4080 | 4 | 4040 | 8 |
M2– 6240 | 2:2:2 | 4080 | 6 | 4040 | 12 |
M2– 8240 | 3:3:2 | 4080 | 8 | 4040 | 16 |
M2–10240 | 3:3:2:2 | 4080 | 10 | 4040 | 20 |
M2–12240 | 3:3:2:2:2 | 4080 | 12 | 4040 | 24 |
SPECIFICATIONS
MODELS | M1– 4240 | M1– 6240 | M1– 8240 | M1–10240 | M1–12240 |
---|---|---|---|---|---|
Design | |||||
Configuration | Single Pass | Single Pass | Single Pass | Single Pass | Single Pass |
Feedwater Source C | TDS < 2,000 ppm | TDS < 2,000 ppm | TDS < 2,000 ppm | TDS < 2,000 ppm | TDS < 2,000 ppm |
Standard Recovery Rate % | 50-75 | 50-75 | 50-75 | 50-75 | 60-75 |
Rejection and Flow RatesD | |||||
Nominal Salt Rejection % | 98.5 | 98.5 | 98.5 | 98.5 | 98.5 |
Permeate Flow (gpm / lpm) | 8.30 / 31.42 | 12.50 / 47.32 | 16.70 / 63.22 | 20.80 / 78.74 | 25.00 / 94.63 |
Minimum Concentrate Flow (gpm / lpm) | 14.30 / 54.00 | 18.50 / 70.00 | 22.70 / 85.93 | 26.80 / 101.45 | 31.00 / 117.35 |
Maximum Feed Flow (gpm / lpm) | 28 / 106 | 28 / 106 | 42 / 159 | 42 / 159 | 42 / 159 |
Minimum Concentrate Flow (gpm / lpm) | 6.00 / 22.70 | 6.00 / 22.70 | 6.00 / 22.70 | 6.00 / 22.70 | 6.00 / 22.70 |
Connections | |||||
Feed (in) | 1.5 FNPT | 1.5 FNPT | 1.5 FNPT | 1.5 FNPT | 1.5 FNPT |
Permeate (in) | 1 FNPT | 1 FNPT | 1 FNPT | 1.5 FNPT | 1.5 FNPT |
Concentrate (in) | 1 FNPT | 1 FNPT | 1 FNPT | 1.5 FNPT | 1.5 FNPT |
CIP (in) | 1 FNPT | 1 FNPT | 1 FNPT | 1 FNPT | 1 FNPT |
Membranes | |||||
Membrane Per Vessel | 2 | 2 | 2 | 2 | 2 |
Membrane Quantity | 8 | 12 | 16 | 20 | 24 |
Membrane Size | 4040 | 4040 | 4040 | 4040 | 4040 |
Vessels | |||||
Vessel Array | 2:2 | 2:2:2 | 3:3:2 | 3:3:2:2 | 3:3:2:2:2 |
Vessel Quantity | 4 | 6 | 8 | 10 | 12 |
Pumps | |||||
Pump Type | Multi-Stage | Multi-Stage | Multi-Stage | Multi-Stage | Multi-Stage |
Motor HP | 3 | 3 | 5 | 7.5 | 7.5 |
RPM at 60 Hz | 3450 | 3450 | 3450 | 3450 | 3450 |
RPM at 50 Hz | 2900 | 2900 | 2900 | 2900 | 2900 |
System Electrical | |||||
Standard Voltage + Amp Draw | 220V, 60Hz, 3PH, 9AE | 220V, 60Hz, 3PH, 9AC | 220V, 60Hz, 3PH, 14.2A | 220V, 60Hz, 3PH, 19.5AC | 220V, 60Hz, 3PH, 19.5AC |
High Voltage Service + Amp Draw |
220V, 50Hz, 3PH, 10.6AE 460V, 60Hz, 3PH, 5AE |
220V, 50Hz, 3PH, 10.6AE 460V, 60Hz, 3PH, 5AE |
220V, 50Hz, 3PH, 16.1AE 460V, 60Hz, 3PH, 7AE |
220V, 50Hz, 3PH, 16.1AE 460V, 60Hz, 3PH, 7AE |
220V, 50Hz, 3PH, 16.1AE 460V, 60Hz, 3PH, 9.7AE |
System Dimensions | |||||
Approximate Dimensions F L x W x H (in /cm) | 31 x 100 x 64 / 787.4 x 254 x 162.56 | 31 x 100 x 64 / 787.4 x 254 x 162.56 | 31 x 100 x 64 / 787.4 x 254 x 162.56 | 31 x 100 x 64 / 787.4 x 254 x 162.56 | 31 x 100 x 64 / 787.4 x 254 x 162.56 |
Approximate Weight (lbs / kg) | 1060 / 480.81 | 1150 / 476.27 | 1260 / 571.53 | 1350 / 612.35 | 1450 / 657.71 |
Test Parameters: : 550 TDS Filtered (5–Micron), Dechlorinated, Municipal Feedwater, 65 psi / 4.50 bar Feed Pressure, 80 psi / 5.5 bar Operating Pressure, 77°F / 25°C, Recovery as stated, 7.0 pH. Data taken after 60 minutes of operation
C. Low temperatures and feedwater quality, such as high TDS
levels will significantly affect the systems production
capabilities and performance. Computer projections must be run for
individual applications which do not meet or exceed minimum and
maximum operating limits for such conditions.
D. Product flow and standard recovery rates are based on feedwater
conditions as stated above. Do not exceed the recommended permeate
flow.
E. Varies with motor manufacturer.
F. Does not include operating space requirements.
OPERATING LIMITSG
Maximum Feed Temperature (°F / °C) | 85 / 29 | Maximum Turbidity (NTU) | 1 |
Maximum Feed Temperature (°F / °C) | 40 / 5 | Maximum Free Chlorine (ppm) | 0 |
Maximum Ambient Temperature (°F / °C) | 120 / 49 | Maximum TDS (ppm) | 2,000 |
Minimum Ambient Temperature (°F / °C) | 40 / 4 | Maximum Hardness (gpg) | 0 |
Maximum Feed Pressure (psi / bar) | 85 / 6 | Maximum pH (continuous) | 11 |
Minimum Feed Pressure (psi / bar) | 45 / 3 | Maximum pH (continuous) | 2 |
Maximum Operating Pressure (psi / bar) | 200 / 14 | Minimum pH (cleaning 30 minutes) | 13 |
Maximum SDI Rating | < 3 | Minimum pH (cleaning 30 minutes) | 1 |
G. If any of the feed water parameters are not within the limits given, consult your local dealer or distributor for assistance.